CAA 636 KCM 26/7F GROSBEAK CL A

Description

Description

Standards

  • National
    ABNT NBR 7270/88

The use of Aluminium as a material for electrical conductors has greatly developed mainly due to its electrical properties. However, Aluminium conductors for most of transmission lines which spans are quite long, it is necessary an additional mechanical support. Commonly it is used galvanized steel wires for cores of ACSR.

 

APPLICATIONS

Widely used as bare cable for overhead transmission lines and also as primary and secondary bare cable for distribution lines.

 

CONSTRUCTION

ACSR is concentrically stranded conductor with one or more layers of Aluminium wire hard-drawn 1350-H19 on the galvanized steel wire core. The core may be single wire or stranded depending on the size. Steel wire is available in Class A or B galvanization as corrosion protection.

ACSR is according to electrical and mechanical strength requirements of transmission or distribution lines, can provides an appropriate design combining the quantity of Aluminium and galvanized steel wires.

 

Conditions for Ampacity calculation

Conductor temperature = 75 °C;

Room temperature = 25 °C;

Wind speed = 1 m/sec, sunny.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Type of cable
Grosbeak
Type of conductor
Circular, stranded
Conductor material
aluminum / Steel Core
Conductor flexibility
Class A
Conductor shape
Circular non compacted

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
636 kcmil
Aluminium cross-section
321.84 mm²
Conductor cross-section
374.33 mm²
Number of aluminium wires
26
Diameter of aluminium wires
3.97 mm
Number of steel wires
7
Diameter of steel wires
3.09 mm
Diameter of steel core
9.27 mm
Conductor diameter
25.15 mm
Average geometric radius
0.01021 m
Aluminium content
894.1 kg/km
Steel content
410 kg/km
Approximate weight
1304 kg/km
Nominal outer diameter
25.15 mm
Number of cores
1
Number of round wires
-

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.09 Ohm/km
Max. electric resisrance AC 60Hz 75°C
0.108 Ohm/km
Inductive reactance
0.3457 Ohm/km
Capacitive reactance
0.2089 MOhm.km
Ampacity
790.0 A

Mechanical characteristics

Mechanical characteristics

Rated breaking load (Class A)
11411 kgf
Rated breaking load (Class B)
11043 kgf
Hardness type
1350-H19

Usage characteristics

Usage characteristics

Length
1870 m
Reel net weight
2435 kg
Packaging
Reel 170/80

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close